Solid-state semi-automatic burner control module without programmer (120V). The fireye D40-41 series burner management controls provide ignition and flame failure protection for manually started oil or gas burners. Plug-in amplifier modules allow selection of ultraviolet, repetitive self-check ultraviolet, auto-check infrared or rectification flame sensing methods. The control system includes a safe start check, effective at every start-up. If a flame signal (real or simulated) is detected, the unit cannot be started. For added safety and reliability, the fireye 72D1R3 auto-check infrared amplifier (using the pulsing flame signal) and 72DUVS ultraviolet amplifier (using a scanner shutter) verify the function of the flame sensing system for component failures during every burner ignition cycle. Meter test jacks on each amplifier module provide flame signal reading with a DC voltmeter. Flame failure response time is four seconds (max). When amplifier modules with T suffix are used, flame failure response time is reduced to one second (max). The control provides three SPDT and one SPNO load switches for external loads and starting circuits. The fireye D40-41 burner management controls can be adapted into a simple control system or as a building block with auxiliary devices to provide additional functions. Note: Image may not be actual representation of item. Specifications: Product Type: Control Module Voltage: 120v